(a) Each fire detection system and each smoke detection system on a unit must—
- (1) Be approved by the Commandant in accordance with 46 CFR 161.002; and
- (2) Have a visual alarm and an audible alarm in the pilothouse or at a normally manned control station for the system.
- (b) Each fire detection system must be divided into zones to limit the area covered by any particular alarm signal.
(c) Each visual alarm must—
- (1) Have a chart or diagram next to the alarm that shows the location of the zones in the system and that contains the instructions for operating, and testing the system;
- (2) When activated show the zone in the system where fire has been detected; and
- (3) Be in a noticeable location in the pilothouse or control station.