- (a) Each enclosed space must be vented or ventilated.
- (b) There must be a means to close each vent or ventilating system.
- (c) Each fan in a ventilating system must have remote controls installed in accordance with part 111, subpart 111.103, of this chapter.
- (d) There must be a means to close each doorway, ventilator, and annular space around each funnel or other opening to machinery, stowage, or working spaces. The means must be located outside the space.
- (e) Each intake in a ventilating system must be located so as to prevent, as far as practicable, the intake of noxious fumes.
[CGD 73-251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 94-108, 61 FR 28270, June 4, 1996]