(c) Each clean agent system must:
- (1) Be of a total flooding type to protect against Class B and Class C hazards as defined in 46 CFR 95.50-5;
- (2) Address and minimize any hazard to personnel created by the effects of extinguishing agent decomposition products and combustion products, especially the effects of decomposition product hydrogen fluoride (HF), if applicable;
- (3) Be accompanied by an approved manufacturer's design, installation, operation, and maintenance manual;
- (4) Be used only to protect enclosed spaces;
- (5) Not employ electric power for system actuation or controls; and
- (6) Not use any source of power for alarms in protected spaces, other than the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.