(a) A protected space must be fitted with an approved audible alarm if:
- (1) The space is normally accessible to persons onboard while the vessel is being navigated; and
- (2) Is not a paint locker or similar small space.
(b) The alarm must:
- (1) Sound automatically and audibly for at least 20 seconds before carbon dioxide is discharged into the space;
- (2) Be conspicuously and centrally located and be marked as required by 46 CFR 97.37-9; and
- (3) Use stored gas power provided by the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.
- (c) For systems installed on or after July 1, 1957, alarms are mandatory only for systems required to be fitted with a delayed discharge.
[USCG-2006-24797, 77 FR 33878, June 7, 2012]