- (a) The smoke detection system must be divided into separate zones to restrict the area covered by any particular alarm signal.
- (b) The smoke detection zone must not include spaces on more than one deck, except the small adjacent spaces mentioned in paragraph (c) of this section.
- (c) Each separate space must be considered as a zone, except that two or three small adjacent spaces having a combined volume not exceeding 5,000 cubic feet may be connected on the same zone.
- (d) Where a space is of such size that one accumulator is not sufficient, not more than two accumulators may be combined in one zone.