- (a) Strainers must be installed in the fuel supply line. Each strainer must be self-cleaning, fitted with a bypass, or be capable of being cleaned without interrupting the fuel oil supply.
- (b) The strainer must not allow a quantity of air to be trapped inside which would affect the rate of fuel flow to the burner or reduce the effective area of the straining element.
- (c) The strainer must meet the requirements for strainers found in UL 296 (incorporated by reference, see § 63.05-1) and the requirements for fluid conditioner fittings found in § 56.15-5 of this subchapter.
[CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008]