(b) Protection of adjacent structure.
- (1) Boilers must be so placed that all parts are readily accessible for inspection and repair.
- (2) In vessels having a double bottom or other extensive surfaces directly below the boiler, the distance between such surface and a boiler must in no case be less than 18 inches at the lowest part.
- (3) The pans of oil-burning, watertube boilers must be arranged to prevent oil from leaking into the bilges and must be lined with firebrick or other heat resisting material.
- (4) The distance between a boiler and a compartment containing fuel oil must not be less than 24 inches.
- (5) All oil-burning boilers must be provided with oiltight drip pans under the burners to prevent oil draining into the bilges.