Portable electric equipment must not be used in a hazardous location described in subpart 111.105 of this chapter except:
- (a) Self-contained, battery-fed, explosion-proof lamps approved by Underwriters Laboratories Inc., Factory Mutual Research Corporation, or other independent laboratory recognized by the Commandant, for use in a Class I, Division 1 location for the electrical group classification of the cargo;
- (b) Intrinsically safe equipment approved by Underwriters Laboratories Inc., Factory Mutual Research Corporation, or other independent laboratory recognized by the Commandant, for use in a Class I, Division 1 location for the electrical group classification of the cargo; and
(c) Any electrical equipment, if:
(1) The hazardous location is:
- (i) Enclosed; and
- (ii) Gas free;
(2) The adjacent compartments are:
- (i) Gas free;
- (ii) Inerted;
- (iii) Filled with water;
- (iv) Filled with Grade E liquid; or
- (v) Spaces where flammable gases are not expected to accumulate; and:
(3) Each compartment where flammable gas is expected to accumulate is:
- (i) Closed; and
- (ii) Secured.
[CGD 74-125A, 47 FR 15230, Apr. 8, 1982]