(g) Each owner or operator must monitor the operation of each enclosed combustor, utility flare, and pit flare to confirm proper operation as follows:
- (1) Continuously monitor all variable operational parameters specified in the written operating instructions and procedures, including continuous burning pilot flame, electronically controlled automatic igniters, and monitoring system failures, using a malfunction alarm and remote notification system, where such systems are available, or continuously monitor under an equivalent alternative protocol upon prior written approval by the EPA;
- (2) Perform a physical inspection of all equipment associated with each enclosed combustor, utility flare, and pit flare each time an operator is on site, at a minimum quarterly, to ensure system integrity;
- (3) Monitor for visible smoke during operation of any enclosed combustor, utility flare or pit flare each time an operator is on site, at a minimum quarterly. Upon observation of visible smoke, use EPA Reference Method 22 of 40 CFR part 60, Appendix A, to determine whether visible smoke emissions are present. The observation period shall be 2 hours. Visible smoke emissions are present if smoke is observed for more than 5 minutes in any 2 consecutive hours; and
- (4) Respond to any observation of any continuous burning pilot flame failure, electronically controlled automatic igniter failure, or improper monitoring equipment operation and ensure the equipment is returned to proper operation as soon as practicable and safely possible after an observation or an alarm sounds.