30 C.F.R. § 18.54
(d) Transformers supplying control voltages.
(2) Transformers with high-voltage primary windings that supply control voltages must incorporate a grounded electrostatic (Faraday) shield between the primary and secondary windings. Grounding of the shield must be as follows:
(e) Onboard ungrounded, three-phase power circuit. A continuous mining machine designed with an onboard ungrounded, three-phase power circuit must:
(f) High-voltage trailing cable(s). High-voltage trailing cable(s) must conform to the ampacity and outer dimensions specified in Table 10 of Appendix I to Subpart D of this part. In addition, the cable must be constructed with:
(4) Either a double-jacketed or single-jacketed cable as follows:
(j) Minimum creepage distances. Rigid insulation between high-voltage terminals (Phase-to-Phase or Phase-to-Ground) must be designed with creepage distances in accordance with the following table:
| Phase-to-phase voltage | Points ofmeasure | Minimum creepage distances (inches) for comparative tracking index (CTI) range 1 | |||
|---|---|---|---|---|---|
| CTI ≥500 | 380 ≤CTI <500 | 175 ≤CTI <380 | CTI <175 | ||
| 2,400 | 0-0 | 1.50 | 1.95 | 2.40 | 2.90 |
| 0-G | 1.00 | 1.25 | 1.55 | 1.85 | |
| 4,160 | 0-0 | 2.40 | 3.15 | 3.90 | 4.65 |
| 0-G | 1.50 | 1.95 | 2.40 | 2.90 | |
| 1 Assumes that all insulation is rated for the applied voltage or higher. |
(k) Minimum free distances. Motor-starter enclosures must be designed to establish the minimum free distance (MFD) between the wall or cover of the enclosure and uninsulated electrical conductors inside the enclosure in accordance with the following table:
| Wall/cover thickness(in) | Steel MFD (in) | Aluminum MFD (in) | ||||
|---|---|---|---|---|---|---|
| A 1 | B 2 | C 3 | A 1 | B 2 | C 3 | |
| 1⁄4 | 2.8 | 4.3 | 5.8 | 4 NA | 4 NA | 4 NA |
| 3⁄8 | 1.8 | 2.3 | 3.9 | 8.6 | 12.8 | 18.1 |
| 1⁄2 | * 1.2 | 2.0 | 2.7 | 6.5 | 9.8 | 13.0 |
| 5⁄8 | * 0.9 | 1.5 | 2.1 | 5.1 | 7.7 | 10.4 |
| 3⁄4 | * 0.6 | * 1.1 | 1.6 | 4.1 | 6.3 | 8.6 |
| 1 | * | * 0.6 | * 1.0 | 2.9 | 4.5 | 6.2 |
| * Note: The minimum electrical clearances must still be maintained in accordance with the minimum clearance table of § 18.24. | ||||||
| 1 Column A specifies the MFD for enclosures that have available three-phase, bolted, short-circuit currents of 10,000 amperes root-mean-square (rms) value or less. | ||||||
| 2 Column B specifies the MFD for enclosures that have maximum available three-phase, bolted, short-circuit currents greater than 10,000 and less than or equal to 15,000 amperes rms. | ||||||
| 3 Column C specifies the MFD for enclosures that have maximum available three-phase, bolted, short-circuit currents greater than 15,000 and less than or equal to 20,000 amperes rms. | ||||||
| 4 Not Applicable—MSHA does not allow aluminum wall or covers to be 1⁄4 inch or less in thickness. (See also § 18.31.) |
(1) For values not included in the table, the following formulas, on which the table is based, may be used to determine the minimum free distance.
(i) Steel Wall/Cover:

(ii) Aluminum Wall/Cover:

Where “C” is 1.4 for 2,400 volt systems or 3.0 for 4,160 volt systems; “Isc” is the three-phase, short-circuit current in amperes of the system; “t” is the clearing time in seconds of the outby circuit-interrupting device; and “d” is the thickness in inches of the metal wall/cover adjacent to an area of potential arcing.
(l) Static pressure testing of explosion-proof enclosures containing high-voltage switchgear—(1) Prototype enclosures. The following static pressure test must be performed on each prototype design of an explosion-proof enclosure containing high-voltage switchgear prior to the explosion tests.
(i) Test procedure.
(ii) Acceptable performance.
(A) During pressurization, the enclosure must not exhibit:
(1) Leakage through welds or casting; or
(2) Rupture of any part that affects the explosion-proof integrity of the enclosure.
(B) Following removal of the pressurizing agents, the enclosure must not exhibit:
(1) Cracks in welds visible to the naked eye;
(2) Permanent deformation exceeding 0.040 inches per linear foot; or
(3) Excessive clearances along flame-arresting paths following retightening of fastenings, as necessary.
(2) Enclosures for production. Every explosion-proof enclosure containing high-voltage switchgear manufactured after the prototype was tested must undergo one of the following tests or procedures:
(ii) An MSHA-accepted quality assurance procedure covering inspection of the enclosure.
(A) The quality assurance procedure must include a detailed check of parts against the drawings to determine that—
(1) The parts and the drawings coincide; and
(2) The requirements stated in part 18 have been followed with respect to materials, dimensions, configuration and workmanship.
[75 FR 17547, Apr. 6, 2010]