29 C.F.R. Appendix D to Subpart P of Part 1926
(c) Presentation of Information. Information is presented in several forms as follows:
(d) Basis and limitations of the data.
(2) Hydraulic cylinders specifications.
(3) Limitation of application.
(ii) When any of the following conditions are present, the members specified in the Tables are not considered adequate. In this case, an alternative aluminum hydraulic shoring system or other type of protective system must be designed in accordance with § 1926.652.
(f) Example to Illustrate the Use of the Tables:
(1) Example 1:
A trench dug in Type A soil is 6 feet deep and 3 feet wide. From Table D-1.1: Find vertical shores and 2 inch diameter cylinders spaced 8 feet on center (o.c.) horizontally and 4 feet on center (o.c.) vertically. (See Figures 1 & 3 for typical installations.)
(2) Example 2:
A trench is dug in Type B soil that does not require sheeting, 13 feet deep and 5 feet wide. From Table D-1.2: Find vertical shores and 2 inch diameter cylinders spaced 6.5 feet o.c. horizontally and 4 feet o.c. vertically. (See Figures 1 & 3 for typical installations.)
(g) Footnotes, and general notes, for Tables D-1.1, D-1.2, D-1.3, and D-1.4.
(3) Hydraulic cylinders capacities.
(10) See appendix D, item (d), for basis and limitations of the data.