29 C.F.R. Appendix C to Subpart P of Part 1926
(c) Presentation of Information. Information is presented in several forms as follows:
(d) Basis and limitations of the data—(1) Dimensions of timber members.
(2) Limitation of application.
(ii) When any of the following conditions are present, the members specified in the tables are not considered adequate. Either an alternate timber shoring system must be designed or another type of protective system designed in accordance with § 1926.652.
(f) Examples to Illustrate the Use of Tables C-1.1 through C-1.3.
(1) Example 1.
A trench dug in Type A soil is 13 feet deep and five feet wide.
From Table C-1.1, for acceptable arrangements of timber can be used.
Arrangement #B1
Space 4 × 4 crossbraces at six feet horizontally and four feet vertically.
Wales are not required.
Space 3 × 8 uprights at six feet horizontally. This arrangement is commonly called “skip shoring.”
Arrangement #B2
Space 4 × 6 crossbraces at eight feet horizontally and four feet vertically.
Space 8 × 8 wales at four feet vertically.
Space 2 × 6 uprights at four feet horizontally.
Arrangement #B3
Space 6 × 6 crossbraces at 10 feet horizontally and four feet vertically.
Space 8 × 10 wales at four feet vertically.
Space 2 × 6 uprights at five feet horizontally.
Arrangement #B4
Space 6 × 6 crossbraces at 12 feet horizontally and four feet vertically.
Space 10 × 10 wales at four feet vertically.
Spaces 3 × 8 uprights at six feet horizontally.
(2) Example 2.
A trench dug in Type B soil in 13 feet deep and five feet wide. From Table C-1.2 three acceptable arrangements of members are listed.
Arrangement #B1
Space 6 × 6 crossbraces at six feet horizontally and five feet vertically.
Space 8 × 8 wales at five feet vertically.
Space 2 × 6 uprights at two feet horizontally.
Arrangement #B2
Space 6 × 8 crossbraces at eight feet horizontally and five feet vertically.
Space 10 × 10 wales at five feet vertically.
Space 2 × 6 uprights at two feet horizontally.
Arrangement #B3
Space 8 × 8 crossbraces at 10 feet horizontally and five feet vertically.
Space 10 × 12 wales at five feet vertically.
Space 2 × 6 uprights at two feet vertically.
(3) Example 3.
A trench dug in Type C soil is 13 feet deep and five feet wide.
From Table C-1.3 two acceptable arrangements of members can be used.
Arrangement #B1
Space 8 × 8 crossbraces at six feet horizontally and five feet vertically.
Space 10 × 12 wales at five feet vertically.
Position 2 × 6 uprights as closely together as possible.
If water must be retained use special tongue and groove uprights to form tight sheeting.
Arrangement #B2
Space 8 × 10 crossbraces at eight feet horizontally and five feet vertically.
Space 12 × 12 wales at five feet vertically.
Position 2 × 6 uprights in a close sheeting configuration unless water pressure must be resisted. Tight sheeting must be used where water must be retained.
(4) Example 4.
A trench dug in Type C soil is 20 feet deep and 11 feet wide. The size and spacing of members for the section of trench that is over 15 feet in depth is determined using Table C-1.3. Only one arrangement of members is provided.
Space 8 × 10 crossbraces at six feet horizontally and five feet vertically.
Space 12 × 12 wales at five feet vertically.
Use 3 × 6 tight sheeting.
Use of Tables C-2.1 through C-2.3 would follow the same procedures.
(g) Notes for all Tables.
1. Member sizes at spacings other than indicated are to be determined as specified in § 1926.652(c), “Design of Protective Systems.”
2. When conditions are saturated or submerged use Tight Sheeting. Tight Sheeting refers to the use of specially-edged timber planks (e.g., tongue and groove) at least three inches thick, steel sheet piling, or similar construction that when driven or placed in position provide a tight wall to resist the lateral pressure of water and to prevent the loss of backfill material. Close Sheeting refers to the placement of planks side-by-side allowing as little space as possible between them.
3. All spacing indicated is measured center to center.
4. Wales to be installed with greater dimension horizontal.
5. If the vertical distance from the center of the lowest crossbrace to the bottom of the trench exceeds two and one-half feet, uprights shall be firmly embedded or a mudsill shall be used. Where uprights are embedded, the vertical distance from the center of the lowest crossbrace to the bottom of the trench shall not exceed 36 inches. When mudsills are used, the vertical distance shall not exceed 42 inches. Mudsills are wales that are installed at the toe of the trench side.
6. Trench jacks may be used in lieu of or in combination with timber crossbraces.
7. Placement cf crossbraces. When the vertical spacing of crossbraces is four feet, place the top crossbrace no more than two feet below the top of the trench. When the vertical spacing of crossbraces is five feet, place the top crossbrace no more than 2.5 feet below the top of the trench.





