29 C.F.R. § 1926.1407
(a) Before assembling or disassembling equipment, the employer must determine if any part of the equipment, load line, or load (including rigging and lifting accessories) could get, in the direction or area of assembly/disassembly, closer than 20 feet to a power line during the assembly/disassembly process. If so, the employer must meet the requirements in Option (1), Option (2), or Option (3) of this section, as follows:
(3) Option (3)—Table A clearance.
(b) Preventing encroachment/electrocution. Where encroachment precautions are required under Option (2), or Option (3) of this section, all of the following requirements must be met:
(3) At least one of the following additional measures must be in place. The measure selected from this list must be effective in preventing encroachment.
The additional measures are:
(i) Use a dedicated spotter who is in continuous contact with the equipment operator. The dedicated spotter must: