(c) Heated water circulation systems must—
- (1) Be provided with a circulation pump;
- (2) Ensure that the system return pipe is a dedicated return pipe or a cold water supply pipe;
- (3) Not include any gravity or thermosyphon circulation systems;
- (4) Ensure that controls for circulating heated water circulation pumps start the pump based on the identification of a demand for hot water within the occupancy; and
- (5) Ensure that the controls automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water.