10 C.F.R. § 460.102
(b) Prescriptive requirements.
(1) The building thermal envelope must meet the applicable minimum R-value (nominal value of insulation), and the glazing maximum U-factor and SHGC, requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(2) or component U-values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5).
| Climate zone | Exterior wallinsulationR-value | Exterior ceilinginsulationR-value | Exterior floorinsulationR-value | WindowU-factor | SkylightU-factor | DoorU-factor | GlazedfenestrationSHGC |
|---|---|---|---|---|---|---|---|
| 1 | 13 | 22 | 22 | 1.08 | 0.75 | 0.40 | 0.7 |
| 2 | 13 | 22 | 19 | 0.5 | 0.55 | 0.40 | 0.6 |
| 3 | 19 | 22 | 22 | 0.35 | 0.55 | 0.40 | Not applicable. |
| Climate zone | Exterior wallinsulationR-value | Exterior ceilinginsulationR-value | Exterior floorinsulationR-value | WindowU-factor | SkylightU-factor | DoorU-factor | GlazedfenestrationSHGC |
|---|---|---|---|---|---|---|---|
| 1 | 13 | 30 | 13 | 0.32 | 0.75 | 0.40 | 0.33 |
| 2 | 21 | 30 | 19 | 0.30 | 0.55 | 0.40 | 0.25 |
| 3 | 21 | 38 | 30 | 0.30 | 0.55 | 0.40 | Not applicable. |
(5) U-factor alternatives to R-value requirements. Compliance with the applicable requirements in paragraph (b)(1) of this section may be determined using the applicable maximum U-factor values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5), which reflect the thermal transmittance of the component, excluding fenestration, and not just the insulation of that component, as an alternative to the minimum nominal R-value requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(1), respectively.
| Climate zone | Exterior ceilingU-factor | Exterior wallU-factor | Exterior floorU-factor |
|---|---|---|---|
| 1 | 0.061 | 0.094 | 0.049 |
| 2 | 0.061 | 0.094 | 0.056 |
| 3 | 0.061 | 0.068 | 0.049 |
| Climate zone | Exterior ceilingU-factor | Exterior wallU-factor | Exterior floorU-factor |
|---|---|---|---|
| 1 | 0.043 | 0.094 | 0.078 |
| 2 | 0.043 | 0.063 | 0.056 |
| 3 | 0.037 | 0.063 | 0.032 |
(c) Performance requirements.
(1) The building thermal envelope must have a Uo that is less than or equal to the applicable value specified in table 5 to § 460.102(c)(1) and table 6 to § 460.102(c)(1).
| Climate zone | Single-sectionUo |
|---|---|
| 1 | 0.110 |
| 2 | 0.091 |
| 3 | 0.074 |
| Climate zone | Multi-sectionUo |
|---|---|
| 1 | 0.082 |
| 2 | 0.066 |
| 3 | 0.055 |
(e) Determination of compliance with paragraph (c) of this section.