10 C.F.R. § 431.446
(a) Each small electric motor manufactured (alone or as a component of another piece of non-covered equipment) after March 9, 2015, or in the case of a small electric motor which requires listing or certification by a nationally recognized safety testing laboratory, after March 9, 2017, shall have an average full load efficiency of not less than the following:
| Motor horsepower/standard kilowatt equivalent | Average full load efficiency | ||
|---|---|---|---|
| Polyphase | |||
| Open motors (number of poles) | |||
| 6 | 4 | 2 | |
| 0.25/0.18 | 67.5 | 69.5 | 65.6 |
| 0.33/0.25 | 71.4 | 73.4 | 69.5 |
| 0.5/0.37 | 75.3 | 78.2 | 73.4 |
| 0.75/0.55 | 81.7 | 81.1 | 76.8 |
| 1/0.75 | 82.5 | 83.5 | 77.0 |
| 1.5/1.1 | 83.8 | 86.5 | 84.0 |
| 2/1.5 | N/A | 86.5 | 85.5 |
| 3/2.2 | N/A | 86.9 | 85.5 |
| Motor horsepower/standard kilowatt equivalent | Average full load efficiency | ||
|---|---|---|---|
| Capacitor-start capacitor-run and capacitor-start induction-run | |||
| Open motors (number of poles) | |||
| 6 | 4 | 2 | |
| 0.25/0.18 | 62.2 | 68.5 | 66.6 |
| 0.33/0.25 | 66.6 | 72.4 | 70.5 |
| 0.5/0.37 | 76.2 | 76.2 | 72.4 |
| 0.75/0.55 | 80.2 | 81.8 | 76.2 |
| 1/0.75 | 81.1 | 82.6 | 80.4 |
| 1.5/1.1 | N/A | 83.8 | 81.5 |
| 2/1.5 | N/A | 84.5 | 82.9 |
| 3/2.2 | N/A | N/A | 84.1 |
(b) For purposes of determining the required minimum average full load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in any table of efficiency standards in paragraph (a) of this section, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows:
[75 FR 10947, Mar. 9, 2010; 75 FR 17036, Apr. 5, 2010]