Cal. Health & Safety Code § 25296
(a) If there has been any unauthorized release, as defined in Section 25294 or subdivision (a) of Section 25295, from an underground storage tank containing motor vehicle fuel not under pressure, the permitholder may repair the tank once by an interior-coating process if the tank meets all of the following requirements:
(1) One of the following tests has been conducted to determine the thickness of the storage tank:
(B) Certification by a special inspector that the shell will provide structural support for the interior lining. The special inspector shall make this certification by entering and inspecting the entire interior surface of the tank and shall base this certification upon the following procedures and criteria:
(ii) If the tank is made of steel, the tank interior surface shall be abrasive blasted completely free of scale, rust, and foreign matter, as specified in the American Petroleum Institute’s recommended practice 16-31, relating to white metal blasting. The special inspection shall sound any perforations or areas showing corrosion pitting with a brass ballpeen hammer to enlarge the perforation or break through a potentially thin steel area. Tanks that have any of the following defects shall not be certified or returned to service:
(C) A test approved by the board as comparable to the tests specified in subparagraph (A) or (B).
If the person conducting the test determines that the test results indicate that the tank has a serious corrosion problem, the local agency may require additional corrosion protection for the tank or may prohibit the permitholder from making the repair.