(a) Use of dust collection systems for the removal of wood dust and chips produced by woodworking machines shall conform to this section.
(1) Suitable dust collection systems shall be required whenever the chips and wood dust produced by woodworking machines accumulate so as to endanger employees.
Note: Additional requirements for all mechanical ventilation systems are contained in Section 5143.
(b) Definitions.
(3) Enclosureless Bag-Type Dust Collector. A dust collector that possess all of the following characteristics:
(c) Location of dust collectors. Dust collectors having a maximum air-handling capacity greater than 500 cubic feet per minute (cfm) shall be located in accordance with one of the following:
(4) Inside of buildings provided that the collectors are enclosureless bag-type dust collectors that meet all the following criteria:
(B) The collector is not used on sanders or abrasive planers having mechanical feeds.
Exception: Mechanically fed abrasive sanders and abrasive planers that meet all of the following conditions:
4. The machine operator shall hand feed stock into the mechanical feed and shall visually inspect the stock for any metal objects which shall be removed before feeding the stock into the machine. The operator shall be in close proximity to the machine to monitor the operation and activate the emergency stop when necessary.
(F) The collector is located at least 20 feet from the nearest emergency egress route.
Exception: One enclosureless bag-type dust collector with a maximum air-handling capacity of 1500 cfm may be located within 20 feet of an emergency egress route provided that it is not within 10 feet of an emergency exit.
(G) The collector is located at least 20 feet from the nearest employee work station.
Exception: One enclosureless bag-type dust collector with a maximum air-handling capacity of 1500 cfm may be located within 20 feet of the nearest employee workstation.
(H) Multiple collectors in the same room are separated from each other by at least 20 ft.
Exception: A maximum of two enclosureless bag-type collectors may be located within 20 feet of each other in the same room provided that each collector has a maximum air-handling capacity of 1500 cfm or less.
(d) Bonding and grounding of ducts. Ducts and flexible hoses used to convey air and materials as part of dust collection systems shall be constructed of metal or other conductive material and shall be bonded and grounded to prevent the accumulation of static electricity generated by the airflow. Nonconductive ducts such as PVC pipes shall not be permitted.
Exception: Nonconductive flexible ducts and hoses may be used for final machine connection in a length not exceeding the minimum required for machine operation provided that bonding to ground is maintained.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. Repealer and new section filed 10-25-74; effective thirtieth day thereafter (Register 74, No. 43).
2. New subsection (c) filed 7-17-75; effective thirtieth day thereafter (Register 75, No. 29).
3. Amendment of subsection (a) filed 8-15-86; effective thirtieth day thereafter (Register 86, No. 41).
4. Amendment of section heading and section filed 11-5-2007; operative 12-5-2007 (Register 2007, No. 45).
5. Editorial correction of subsection (c)(4) (Register 2008, No. 43).