Cal. Code Regs. tit. 8, § 5593
(e) For tanks and storage vessels designed for pressures over 1 psig, the total rate of venting shall be determined in accordance with Table FL-16, except that when the exposed wetted area of the surface is greater than 2,800 sq. ft., the total rate of venting shall be in accordance with Table FL-17 or calculated by the following formula:
CFH = 1,107 A0.82
Where:
CFH = venting requirement, in cubic feet of free air per hour.
A = exposed wetted surface, in square feet.
The foregoing formula is based on Q = 21,000 A0.82
(f) The total emergency relief venting capacity for any specific stable liquid may be determined by the following formula:
Cubic feet of free air per hour = V
1337
L✓M.
V = cubic feet of free air per hour from Table FL-16.
L = latent heat of vaporization of specific liquid in BTU per pound.
M = molecular weight of specific liquids.
Table FL-16 Wetted Area Versus Cubic Feet Free Air Per Hour* (14.7 psig and 60°F.)
Sq. Ft.
CFH
Sq. Ft.
CFH
Sq. Ft.
CFH
20
21,100
200
211,000
1,000
524,000
30
31,600
250
239,000
1,200
557,000
40
42,100
300
265,000
1,400
587,000
50
52,700
350
288,000
1,600
614,000
60
63,200
400
312,000
1,800
639,000
70
73,700
500
354,000
2,000
652,000
80
84,200
600
392,000
2,400
704,000
90
94,800
700
428,000
2,800
742,000
100
105,000
800
462,000
see (e)
120
126,000
900
493,000
140
147,000
1,000
524,000
160
168,000
180
190,000
200
211,000
* Interpolate for intermediate values.
Table FL-17
Sq. Ft.
CFH
Sq. Ft.
CFH
2,800
742,000
9,000
1,930,000
3,000
786,000
10,000
2,110,000
3,500
892,000
15,000
2,940,000
4,000
995,000
20,000
3,720,000
4,500
1,100,000
25,000
4,470,000
5,000
1,250,000
30,000
5,190,000
6,000
1,390,000
35,000
5,900,000
7,000
1,570,000
40,000
6,570,000
8,000
1,760,000
(g) For tanks containing stable liquids, the required air-flow rate of (d) or (f) may be multiplied by the appropriate factor listed in the following schedule when protection is provided as indicated. Only one factor may be used for any one tank.
(1) Insulation systems for which credit is taken shall meet the following performance criteria and shall be subject to approval of the authority having jurisdiction:
.5 For drainage in accordance with Section 5595(b) for tanks over 200 square feet of wetted area.
.3 For approved water spray in accordance with Standard for Water Spray Fixed Systems for Fire Protection, NFPA No. 15, and drainage in accordance with Section 5595(b).
.3 For approved insulation in accordance with (g)(1).
.15 For approved water spray with approved insulation in accordance with (g)(1) and drainage in accordance with Section 5595(b).
(i) Each commercial tank venting device shall have stamped on it the opening pressure, the pressure at which the valve reaches the full open position and the flow capacity at the latter pressure. If the start to open pressure is less than 2.5 psig and the pressure at full open position is greater than 2.5 psig, the flow capacity at 2.5 psig shall also be stamped on the venting device. The flow capacity shall be expressed in cubic feet per hour of air at 60 F. and 14.7 psia.
(2) A suitable formula for this calculation is:
CFH = 1,667 CfA✓(Pt - Pa)
where CFH = venting requirement in cubic feet of free air per hour
Cf = 0.5 (the flow coefficient)
A = the orifice are in sq. in.
Pt = the absolute pressure inside the tank in inches of water
Pa = the absolute atmospheric pressure outside the tank in inches of water
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. Amendment of subsection (b) and new Note filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).