Cal. Code Regs. tit. 8, § 5589
(a) Every aboveground tank for the storage of Category 1, 2, 3 or 4 flammable liquids, except those liquids with boil-over characteristics and unstable liquids, operating at pressures not in excess of 2.5 psig and designed with a weak roof-to-shell seam or equipped with emergency venting devices which will not permit pressures to exceed 2.5 psig, shall be located in accordance with Table FL-10.
(g) Where end failure of horizontal pressure tanks and vessels may expose property, the tank shall be placed with the longitudinal axis parallel to the nearest important building.
Table FL-10
Type of Tank
Protection
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way and Shall Be Not Less Than Five (5) Feet
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building and Shall Be Not Less Than Five (5) Feet
Floating Roof
Protection for Exposures
½ times diameter of tank but need not exeed 90 feet
1/6 times diameter of tank but need not exceed 30 feet
None
Diameter of tank but need not exceed 175 feet
1/6 times diameter of tank but need not exceed 30 feet
Vertical with Weak Roof to Shell Seam
Approved foam or inerting system on the tank
½ times diameter of tank but need not exceed 90 feet
1/6 times diameter of tank but need not exceed 30 feet
Protection for Exposures
Diameter of tank but need not exceed 175 feet
⅓ times diameter of tank but need not exceed 60 feet
None
2 times diameter of tank but need not exceed 350 feet
⅓ times diameter of tank but need not exceed 60 feet
Horizontal and Vertical, with Emergency Relief Venting to Limit Pressures to 2.5 psig
Approved inerting system on the tank or approved foam system on vertical tanks
½ times Table FL-15
½ times Table FL-15
Protection for Exposures
Table FL-15
Table FL-15
None
2 times Table FL-15
Table FL-15
Table FL-11
Type of Tank
Protection
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Any Type
Protection for Exposures
1 ½ times Table FL-15 but shall not be less than 25 feet
1 ½ times Table FL-15 but shall not be less than 25 feet
None
3 times Table FL-15 but shall not be less than 50 feet
1 ½ times Table FL-15 but shall not be less than 25 feet
Table FL-12
Type of Tank
Protection
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Floating Roof
Protection for Exposures
½ times diameter of tank but need not exceed 90 feet
1/6 times diameter of tank but need not exceed 30 feet
None
Diameter of tank but need not exceed 175 feet
1/6 times diameter of tank but need not exceed 30 feet
Fixed Roof
Approved foam or inerting system
Diameter of tank but need not exceed 175 feet
⅓ times diameter of tank but need not exceed 60 feet
Protection for Exposures
2 times diameter of tank but need not exceed 350 feet
2/3 times diameter of tank but need not exceed 120 feet
None
4 times diameter of tank but need not exceed 350 feet
2/3 times diameter of tank but need not exceed 120 feet
Table FL-13
Type of Tank
Protection
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Horizontal and Vertical Tanks With Emergency Relief Venting to Permit Pressure Not in Excess of 2.5 psig
Tank protected with any one of the following: Approved water spray, Approved inerting, Approved insulation and refrigeration, Approved barricade
Table FL-15 but not less than 25 feet
Not less than 25 feet
Protection for Exposures
2 ½ times Table FL-15 but not less than 50 feet
Not less than 50 feet
None
5 times Table FL-15 but not less than 100 feet
Not less than 100 feet
Horizontal and Vertical Tanks With Emergency Relief Venting to Permit Pressure
Tank protected with any one of the following: Approved water spray, Approved inerting, Approved insulation and refrigeration, Approved barricade
2 times Table FL-15 but not less than 50 feet
Not less than 50 feet
Protection for Exposures
4 times Table FL-15 but not less than 100 feet
Not less than 100 feet
None
8 times Table FL-15 but not less than 150 feet
Not less than 150 feet
Table FL-14
Capacity Gallons
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
12,000 or less
5
5
12,001 to 30,000
10
5
30,001 to 50,000
10
10
50,001 to 100,000
15
10
100,001 or more
15
15
Table FL-15
Capacity Tank Gallons
Minimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way
Minimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
275 or less
5
5
276 to 750
10
5
751 to 12,000
15
5
12,001 to 30,000
20
5
30,001 to 50,000
30
10
50,001 to 100,000
50
15
100,001 to 500,000
80
25
500,001 to 1,000,000
100
35
1,000,001 to 2,000,000
135
45
2,000,001 to 3,000,000
165
55
3,000,001 or more
175
60
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.