Cal. Code Regs. tit. 8, § 5530
(c) Where the provisions of this article require the installation of electrical equipment suitable for Class I, Division 1 or Division 2 locations, ordinary electrical equipment including switchgear may be used if installed in a room or enclosure which is maintained under positive pressure with respect to the classified area. Ventilation make-up air shall be uncontaminated by flammable vapors.
Scope. This article shall apply to the following areas where:
1) Category 1, 2, or 3 liquids with a flash point below 100 °F (37.8 °C) (formerly designated as Class I) are stored or handled.
2) Category 3 liquids with a flash point greater than or equal to 100 °F (37.8 °C) and less than 140 °F (60 °C)(formerly designated as Class II) are stored or handled at or above their flash point.
3) Category 4 liquids or liquids with a flash point greater than or equal to 199.4 °F (93 °C) (both formerly designated as Class III) are stored or handled at temperatures at or above their flash points.
For areas where only Category 3 liquids with a flash point greater than or equal to 100 °F (37.8 °C) or Category 4 liquids or liquids with a flash point greater than or equal to 199.4 °F (93 °C) are stored or handled at a temperature below their flash points, the electrical equipment may be installed in accordance with the provisions of the California Electrical Safety Orders for ordinary locations; however, care shall be used in locating electrical apparatus to prevent hot metal from falling into open equipment.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.