Cal. Code Regs. tit. 8, § 5154.1
(a) Scope. When laboratory-type hoods, also known as laboratory fume hoods, as defined below are used to prevent harmful exposure to hazardous substances, such hoods shall conform to all applicable provisions of Article 107, and shall conform to provisions of this section.
Exception No. 1: Inspection doors or clean-out doors in exhaust ducts required by Section 5143(a)(3) do not apply to laboratory-type hood operations.
Exception No. 2: Biological safety cabinets as defined below are exempt from the requirements of this section. Class II biological safety cabinets may be used to prevent harmful exposure to cytotoxic agents during their compounding or preparation for parenteral use. Biological safety cabinets may be used to control harmful exposure to aerosols and particulate matter, provided the presence of the substance in the biological safety cabinet does not present a risk of fire or explosion. When biological safety cabinets are used to control exposure to these hazards they shall meet the requirements of Section 5154.2.
(b) Definitions.
Biohazard agent means a replication capable pathogen which is a disease causing microorganism and is capable of causing diseases in humans including viruses, microbes and sub viral agents. The agent includes the agent, products of infectious agents, or the components of infectious agents presenting a risk of illness or injury.
Biohazardous materials are any materials that would harbor biohazardous agents such as human blood, body fluids, or tissues that may be contaminated with biohazardous agents.
Biological safety cabinet. A ventilated cabinet which serves as a primary containment device for operations involving biohazard agents or biohazardous materials. Three classes of biological safety cabinets are described in Section 5154.2.
Hazardous Substance. One which by reason of being explosive, flammable, poisonous, an irritant, or otherwise harmful is likely to cause injury or illness if not used with effective control methods.
Laboratory-Type Hood. A device enclosed except for necessary exhaust purposes on three sides and top and bottom, designed to draw air inward by means of mechanical ventilation, operated with insertion of only the hands and arms of the user, and used to control exposure to hazardous substances. These devices are also known as laboratory fume hoods.
(c) Ventilation Rates.
(2) When a laboratory-type hood is in use to contain airborne hazardous substances and no employee is in the immediate area of the hood opening, the ventilation rate may be reduced from the minimum average face velocity of at least 100 feet per minute to a minimum average face velocity of 60 feet per minute if the following conditions are met:
(B) The laboratory-type hood has been tested at the reduced flow rate according to the tracer gas method specified in Section 7, Tracer Gas Test Procedure, of ANSI/ASHRAE 110-1995, Method of Testing Performance of Laboratory Fume Hoods, which is hereby incorporated by reference, and has a hood performance rating of 4.0 AU 0.1 or less. The test may be performed with or without the mannequin described in the ANSI/ASHRAE 110-1995 tracer gas method.
The tracer gas test need only be performed once per hood. However, if employers have chosen to perform the tracer gas test on subsequent occasions, it is the most recent record of test results and test configuration that shall be maintained pursuant to subsection (c)(2)(C).
(e) Special Requirements.
(3) In addition to being tested as required by Section 5143(a)(5), hoods shall meet the following requirements:
(B) Qualitative airflow measurements that indicate the ability of the hood to maintain an inward airflow at all openings of the hood as required by subsection (c)(1) shall be demonstrated using smoke tubes or other suitable qualitative methods. This demonstration shall be performed:
2. On an annual basis;
Exception to Subsection (3)(B)2.: The frequency of the tests may be reduced to every two years if a calibration and maintenance program is in place for the quantitative airflow monitor or alarm system.
(4) Exhaust stacks shall be located in such a manner with respect to air intakes as to preclude the recirculation of laboratory-type hood emissions within a building. To protect employees on the roof, any one of the follow methods shall be utilized:
(D) Exhaust stacks extending at least 7 feet above the roof and discharging vertically upward. Where rain protection is desired, high velocity discharge or concentric-duct, self-draining stacks (Figure V-9) or equivalent may be used. Rain caps which divert the exhaust toward the roof are prohibited.
FIGURE V-9
EXAMPLE OF A CONCENTRIC-DUCT SELF-DRAINING STACK
)
(7) When perchloric acid is evaporated in laboratory-type hoods, the provisions of Section 5143(a)(4) shall apply. The materials of construction shall be inert, smooth, and nonabsorbent. Organic polymers shall not be used except for inert fluoropolymers, such as polytetrafluoroethylene [PTFE] and tetrafluoroethylene-hexafluoropropylene copolymer [Teflon FEP], or similar nonreactive material. The hood and exhaust system shall be washed down with water for decontamination and prior to opening for maintenance.
Exception: Portable laboratory scrubbing apparatus for perchloric acid digestions may be used in lieu of the special requirements of this paragraph.
(f) Operator Qualifications. The employer shall ensure that employees who use laboratory-type hoods are trained to:
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. New section filed 8-12-76; effective thirtieth day thereafter (Register 76, No. 33).
2. Editorial correction of subsection (e)(4) (Register 76, No. 48).
3. Amendment of subsections (b) and (e)(4) filed 4-16-80; effective thirtieth day thereafter (Register 80, No. 16).
4. Amendment filed 10-11-94; operative 11-10-94 (Register 94, No. 41).
5. Amendment filed 7-31-2006; operative 8-30-2006 (Register 2006, No. 31).
6. Change without regulatory effect providing more legible illustration for Figure V-9 filed 3-2-2009 pursuant to section 100, title 1, California Code of Regulations (Register 2009, No. 10).