Cal. Code Regs. tit. 8, § 5153
(b) Operation.
(c) Exhaust and Make-Up Air.
(e) Ventilation Rates. The velocity of air into all openings of a spray booth shall be not less than that specified in Table V-6.
TABLE V-6 MINIMUM MAINTAINED VELOCITIES INTO SPRAY BOOTHS
Operating Conditions for Objects Completely Inside
Crossdraft,
Airflow Velocities, f.p.m.
Booth
f.p.m.
Average
Minimum
Electrostatic and automatic airless operation
Up to 50
60 large booth
60
100 small booth
75
Air-operated guns, manual or automatic
Up to 50
100 large booth
75
150 small booth
125
Air-operated guns, manual or automatic
From 50 to 100
150 large booth
125
200 small booth
150
Note: A large booth is a walk-in size booth.
(f) Downdraft Booths.
Where downdraft booths are provided with doors, such doors shall be closed when spray painting.
(g) Respiratory Protection.
A spray booth operator is required to wear a respirator when he is positioned downstream from the object being sprayed. Respirator use shall conform to the requirements of Section 5144. (Title 24, T8-5153(a), (b), (c), (d), (e))
Note: Authority cited: Section 142.3, Labor Code.