- (a) Each generating chamber shall be provided with an escape or relief pipe, installed without traps so that any condensate will drain back into the chamber.
- (b) All relief pipes shall be carried to a suitable point outside the building and shall terminate in a suitable hood or bend located at least 12 feet above the ground and at least three feet from combustible construction. Each generator shall be provided with a vent pipe of Schedule 40 galvanized iron or steel, or equivalent.
- (c) Generating chamber relief pipes shall not be interconnected but shall be led separately to the outside air.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.