Cal. Code Regs. tit. 8, § 4805
(b) Generators installed inside buildings shall be enclosed in a separate room. The walls, partitions, floors, and ceilings of inside general rooms shall be of construction having a fire-resistance rating of at least one-hour.
The walls or partitions shall be continuous from floor to ceiling and shall be securely anchored. At least one wall of the room shall be an external wall.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.