(a) Periodic testing shall comply with the parts of ASME A17.1-2004, section 8.11, that are applicable for the type of conveyance involved with the following frequencies:
- (1) Category One Tests shall be completed once every 12 months;
- (2) Category Three Tests shall be completed once every 36 months; and
- (3) Category Five Tests shall be completed once every 60 months.
- (b) Whenever a Category One Test is performed, the test procedure shall include earthquake protective devices in addition to the items specified by ASME A17.1-2004, section 8.11.
- (c) Test tags per ASME A17.1-2004, section 8.11.1.6, are required. Tags shall be installed in a machinery space when machine rooms are not available.
- (d) Periodic tests shall be conducted by a Certified Competent Conveyance Mechanic (CCCM) employed by a Certified Qualified Conveyance Company (CQCC).
(e) Periodic tests shall be witnessed, as required by ASME A17.1-2004, section 8.11.1.1.2, by a Certified Competent Conveyance Inspector (CCCI) or by a Division CCCI. Periodic tests witnessed by a CCCI shall be reported to the Division by the CCCI on a form provided by the Division, or equivalent, within 21 days of the test. The information required to be reported shall include:
- (1) The name of the CCCI witnessing the test;
- (2) Type of test performed as contained in ASME A17.1-2004, section 8.11;
- (3) Name of the CQCC and CCCM who performed the test;
- (4) The date of the test; and
- (5) Results of the test.
- (f) All statements on the form shall be made under penalty of perjury.
- (g) If an elevator fails a periodic test, it shall be removed from service until a satisfactory test result is achieved.
Note: Authority cited: Sections 142.3 and 7323, Labor Code. Reference: Sections 142.3 and 7323, Labor Code.