Cal. Code Regs. tit. 8, § 3120.0
(b) Screening of Hoistway.
(1) When two or more elevators are located in the same hoistway, the elevators shall be fully separated by a material complying with the following:
(D) Be so supported and braced that when subjected to a pressure of 100 lb/ft2 (4.79 kPa) applied horizontally at any point, the deflection shall not exceed 1in. (25.4mm).
Note: Screening is subject to local building code requirements.
(Title 24, Part 7, Section 7-3120.0 )
Construction of hoistways and hoistway enclosures shall comply with Section 100 of ASME A17.1-1996; except for Rules 100.1a(3) and 100.1c(3); which is hereby incorporated by reference.