Cal. Code Regs. tit. 8, § 2756
(2) For intermediate values of system voltage, use next higher voltage in table.
(Title 24, Part 3, Section 3-710-33.)
Minimum spacing for bare conductors shall be in accordance with Table 2756, although greater spacing may be required by unusual atmospheric or other special conditions.
Table 2756
Minimum Spacing in Inches Between Bare Energized Parts and Adjacent Surfaces
Voltage
Outdoor
Indoor
Phase to Phase
Phase to Ground
Phase to Phase
Phase to Ground
Phase to Phase
601
3 ½
5
¾
¾
750
3 ½
5
¾
¾
1200
3 ½
5
1 ¼
1 ¼
2500
3 ½
5
2
2 ½
5000
6
7
2 ½
4
7500
6
7
4
5
15000
7
12
6
7
23000
10
15
10
15
35000
13
18
13
18
Above 35 KV
.37/KV
.455/KV
36 /KV
.455 /KV
NOTES:
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 1210-87; operative 1-9-88 (Register 88, No. 1).