Cal. Code Regs. tit. 8, § 2730
(c) Both switches have a common electrical or mechanical tripping arrangement.
Exception: Both switches need not have a common tripping arrangement if continuity of service requires that both switches not be tripped together, under fault conditions, and a suitable relay protection scheme is employed to separate faulted portions from the system.
(d) Both switches can be padlocked in the open position.
(Title 24, Part 3, Section 3-230-214.)
When the load of an existing service entrance switch increases beyond its continuous current rating or continuity of service requires, a second service entrance switch of identical rating shall be permitted to be connected in parallel with it, provided:
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).