Cal. Code Regs. tit. 8, § 2934
Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:
Table 2934 - Elevation of Unguarded Live Parts above Workspace
NOMINAL VOLTAGE
ELEVATION
BETWEENPHASES
Feet
Meters
601-7500
9.01
2.81
7501-35kV
9.0
2.8
Over 35kv
9 feet + 0.37 inch/kv
2.8 + 9.5 mm/kV
above 35kv
over 35 kV
1 The minimum elevation may be 8.5 ft. (2.6 m) for installations built before April 1, 2009.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.