Cal. Code Regs. tit. 8, § 2932
(a) The minimum depth of clear working space about electrical equipment, such as switchgear, motor controllers, etc., shall not be less than set forth in Table 2932 unless otherwise specified in these orders. Clearances shall be measured from the energized parts if parts are exposed or from the enclosure front or opening, if parts are enclosed.
Table 2932 -- Minimum Depth of Clear Working Space at Electric Equipment, Over 600 Volts
Nominal
MINIMUM CLEAR DISTANCE FOR CONDITIONS
Voltage to
Condition 1
Condition 2
Condition 3
Ground
Feet
Meters
Feet
Meters
Feet
Meters
601-2500
3
0.9
4
1.2
5
1.5
2501-7500
4
1.2
5
1.5
6
1.8
7501-25,000
5
1.5
6
1.8
9
2.8
25,001-75kv
6
1.8
8
2.5
10
3.0
Above 75kv
8
2.5
10
3.0
12
3.7
Where the conditions are as follows:
Condition 1 Exposed energized parts on one side and no energized or grounded parts on the other side of the working space, or exposed energized parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at not over 300 volts are not considered energized parts. Non-shielded insulated conductors shall be considered as exposed energized parts.
Condition 2 Exposed energized parts on one side and grounded parts on the other side. Concrete, brick, plaster, or tile walls will be considered as grounded surfaces.
Condition 3 Exposed energized parts on both sides of the workspace (not guarded as provided in Condition 1) with the operator between.
Exceptions:
(d) The following requirements apply to the entrances to all buildings, rooms, or enclosures containing exposed energized parts or exposed conductors operating at over 600 volts, nominal:
(2) Permanent and conspicuous warning signs shall be provided, reading substantially as follows:
“DANGER -- HIGH VOLTAGE -- KEEP OUT.”
(e) Pipes or ducts that are foreign to the electrical installation and that require periodic maintenance or whose malfunction would endanger the operation of the electrical system may not be located in the vicinity of service equipment, metal-enclosed power switchgear, or industrial control assemblies. Protection shall be provided where necessary to avoid damage from condensation leaks and breaks in such foreign systems.
Note to subsection 2932(e): Piping and other facilities are not considered foreign if provided for fire protection of the electrical installation.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.