- (a) Each generator shall be provided with a load switching device meeting the requirements of Section 2833 or 2837. A properly coordinated and rated combination of current-limiting fuses and contactor will meet this requirement.
- (b) Isolation. A means shall be installed to isolate each generator from all sources of potential. The isolating means shall meet the requirements of Section 2835 (b).
- (c) Excitation Control. The generator excitation system shall include a means for safely interrupting excitation current.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.