- (a) The continuous current rating of a circuit breaker shall equal or exceed the maximum continuous current at the point of installation.
- (b) The interrupting rating of a circuit breaker shall equal or exceed the maximum fault current the circuit breaker will be required to interrupt, including contributions from all connected sources of energy.
- (c) The closing rating of a circuit breaker shall equal or exceed the maximum asymmetrical fault current into which the circuit breaker can be closed.
- (d) The momentary rating of a circuit breaker shall equal or exceed the maximum asymmetrical fault current at the point of installation.
(e) The rated maximum voltage of a circuit breaker shall equal or exceed the maximum circuit voltage.
(Title 24, Part 3, Section 710-21(a)(5)-(a)(9).)