Cal. Code Regs. tit. 8, § 2835
(b) Isolating Means. A suitable air break switching device shall be installed to isolate each oil switch or group of oil switches from all sources of supply unless automatic disconnecting switchgear equipment of the metal-clad draw-out type is used.
Exception: In highly corrosive or flammable atmospheres, suitable isolating means other than air break shall be used, or the isolating means shall be installed in an enclosure approved for use in such locations of the particular hazard involved.
(d) Accessible to Other Than Qualified Persons. Disconnecting switches installed in any location where other than qualified persons have access shall be installed in suitable enclosures.
The door or cover of the enclosure shall be kept closed, except when opened for operation or inspection. If installed so that the bottom of the enclosure is less than 8 feet above the floor, the door or cover shall be kept locked.
When disconnecting switches are operable from outside the enclosure by a remote control mechanism, the operating handle or lever shall be kept locked when in either the open or closed position.
(e) Operation. Isolating switches shall be provided with suitable means for safe normal operation. This operating means shall be permitted to be an insulated hookstick, an insulated external operating handle, or remote control mechanism. Disconnecting switches shall provide a visible gap in the circuit adequate for the operating voltage.
Provision shall be made to observe the position of the blades of disconnecting switches. If viewing windows are provided, they shall be shatterproof, of adequate size, and suitably located to permit viewing of all contacts. Metal-enclosed switches other than those designed for hookstick operation shall be arranged to be locked in the open position. Multiple switches in the same enclosure shall be equipped with a connection diagram.
(i) Barriers. Suitable barriers shall be installed on both sides of each pole of disconnecting switches mounted indoors.
(Title 24, Part 3, Section 3-710-22.)
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.