(a) Circuits supplying power to ungrounded receptacles for hand-held, cord- and plug-connected equipment shall meet the following requirements:
- (1) The circuits shall be electrically isolated from any distribution system supplying areas other than the cell line working zone and shall be ungrounded;
- (2) The circuits shall be supplied through isolating transformers with primaries operating at not more than 600 volts between conductors and protected with proper overcurrent protection;
- (3) The secondary voltage of the isolating transformers may not exceed 300 volts between conductors; and
- (4) All circuits supplied from the secondaries shall be ungrounded and shall have an approved overcurrent device of proper rating in each conductor.
- (b) Receptacles and their mating plugs for ungrounded equipment may not have provision for a grounding conductor and shall be of a configuration that prevents their use for equipment required to be grounded.
(c) Receptacles on circuits supplied by an isolating transformer with an ungrounded secondary:
- (1) Shall have a distinctive configuration;
- (2) Shall be distinctively marked; and
- (3) Shall not be used in any other location in the facility.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.