Cal. Code Regs. tit. 8, § 2375.19
(a) Over roofs. Open wiring and cables shall have a clearance of not less than 8 feet from the highest point of roofs over which they pass.
Exception: No. 1: Where the voltage between conductors does not exceed 300 and the roof has a slope of not less than 4 inches in 12 inches, a reduction in clearance to 3 feet shall be permitted.
Exception: No. 2: Where the voltage between conductors does not exceed 300, a reduction in clearance over the overhanging portion of the roof to 18 inches shall be permitted if:
b. They are terminated at a (through-the-roof) raceway or approved support.
Exception: No. 3: The area above a roof surface subject to pedestrian or vehicular traffic shall have a vertical clearance from the roof surface in accordance with the clearance requirements of Section 2375.18.
(c) Final Spans.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.