Cal. Code Regs. tit. 8, § 2375.18
Open conductors, open multiconductor cables, and service-drop conductors of not over 600 volts, nominal, shall conform to the following minimum clearances:
Installations built before May 5, 2008:
Above areas (other than thoroughfares) where it is possible to drive vehicles
16 feet (4.88 m)
Above areas accessible to pedestrians only
12 feet (3.66 m)
Installations built on or after May 5, 2008:
Table 2375.18 Clearances from Ground.
Installations built on or after May 5, 2008
Distance
Voltage to ground
Conditions
12 ft. (3.66 m)
<300V
Above finished grade or sidewalks, or from any platform or projection from which they might be reached. Over residential property and driveways. Over commercial areas subject to pedestrian traffic or to vehicular traffic other than truck traffic.
16 ft. (4.88 m)
301 to 600 V
Over residential property and driveways. Over commercial areas subject to pedestrian traffic or to vehicular traffic other than truck traffic. (This category includes conditions covered under the 12 ft. (3.66 m) category where the voltage exceeds 300 V.)
18 ft. (5.49 m)
<600 V
Note: California Public Utilities Commission (CPUC) General Order No. 95 applies in areas subject to CPUC jurisdiction
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.