- (a) A ground-fault circuit interrupter shall be installed in the branch circuit supplying underwater fixtures operating at more than 15 volts. Equipment installed underwater shall be identified for the purpose.
- (b) No underwater lighting fixtures may be installed for operation at over 150 volts between conductors.
- (c) A lighting fixture facing upward shall have the lens adequately guarded to prevent contact by any person.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
History
1. New section filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).
2. Amendment of section heading, section and Note filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).