Cal. Code Regs. tit. 8, § 2569.5
(c) For installations built on or after May 5, 2008 where a pool is installed permanently at a dwelling unit, at least one 125-volt, 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located a minimum of 10 feet (3.05 m) and not more than 20 feet (6.08 m) from the inside wall of the pool. This receptacle shall be located not more than 6.5 feet (1.98 m) above the floor, platform, or grade level serving the pool.
Note: In determining these dimensions, the distance to be measured is the shortest path the supply cord of an appliance connected to the receptacle would follow without piercing a floor, wall, or ceiling of a building or other effective permanent barrier.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. New section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).