(a) The following are acceptable protection techniques for electric and electronic equipment in hazardous (classified) locations.
- (1) Explosion-proof apparatus. This protection technique is permitted for equipment in the Class I, Division 1 and 2 locations for which it is approved.
- (2) Dust ignition-proof. This protection technique is permitted for equipment in the Class II, Division 1 and 2 locations for which it is approved.
- (3) Dust-tight. This protection technique is permitted for equipment in the Class II, Division 2 and Class III locations for which it is approved.
- (4) Purged and pressurized. This protection technique is permitted for equipment in any hazardous (classified) location for which it is approved.
- (5) Nonincendive circuit. This protection technique is permitted for equipment in Class I, Division 2; Class II, Division 2; or Class III, Division 1or 2 locations.
- (6) Nonincendive equipment. This protection technique is permitted for equipment in Class I, Division 2; Class II, Division 2; or Class III, Division 1 or 2 locations.
- (7) Nonincendive component. This protection technique is permitted for equipment in Class I, Division 2; Class II, Division 2; or Class III, Division 1 or 2 locations.
- (8) Oil immersion. This protection technique is permitted for current-interrupting contacts in Class I, Division 2 locations as described in these Orders.
- (9) Hermetically sealed. This protection technique is permitted for equipment in Class I, Division 2; Class II, Division 2; and Class III, Division 1 or 2 locations.
- (10) Other protection techniques. Any other protection technique that meets Section 2540.3 of these Orders is acceptable in any hazardous (classified) location.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
History
1. Editorial correction of Note filed 11-2-83 (Register 83, No. 45).
2. Editorial correction filed 11-3-83 (Register 83, No. 45).
3. Amendment filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).
4. Amendment of section heading, repealer and new section and amendment of Note filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).