Cal. Code Regs. tit. 8, § 2510.1
d. Integral lighting switches, if used, shall not be readily accessible.
Exception: No. 2: The supply voltage may exceed 300 volts for permanently installed fixtures at a height of 18 feet or more.
Voltage to Ground. Lampholders, fixtures, or standard receptacles rated 15 amperes or less shall not be supplied by voltages exceeding 150 volts to ground.
Exception: No. 1: Supply voltages between 150 and 300 volts to ground shall be permitted provided all of the following conditions are met: a. Only qualified persons will service the lighting fixtures;
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.