Cal. Code Regs. tit. 8, § 2485.1
(a) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 0.25 in. (6.35 mm) airspace between the enclosure and the wall or other supporting surface.
Exception: Nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.