(a) Single conductor cable.
- (1) Single conductor cable shall be No. 1/0 or larger and shall be of a type listed and marked on the surface for use in cable trays; where Nos. 1/0 through 4/0 single conductor cables are installed in ladder cable tray, the maximum allowable rung spacing for the ladder cable tray shall be 9 in. (229 mm); where exposed to direct rays of the sun, cables shall be identified as being sunlight resistant;
- (2) Welding cables installed in dedicated cable trays;
- (3) Single conductors used as equipment grounding conductors; these conductors, which may be insulated, covered, or bare, shall be No. 4 or larger; and
- (b) Multiconductor cable, Type MV; where exposed to direct rays of the sun, the cable shall be identified as being sunlight resistant.
In industrial establishments where conditions of maintenance and supervision assure that only qualified persons will service the installed cable tray system, the following cables may also be installed in ladder, ventilated-trough, or ventilated-channel cable trays:
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.