Cal. Code Regs. tit. 8, § 1931
(c) Storage in inside storage rooms shall comply with the following:
Automatic Fire Protection* Provided
Fire Resistance
Maximum Floor Area
Total Allowable Quantities Gals./sq. ft./floor area
yes
2-hour
500 sq. ft.
10
no
2-hour
500 sq. ft.
4
yes
1-hour
150 sq. ft.
5
no
1-hour
150 sq. ft.
2
* Fire protection system shall be sprinkler, water spray, carbon dioxide, or other system approved by a nationally recognized testing laboratory for this purpose.
(e) Provisions shall be made for ventilation of inside storage rooms in accordance with General Industry Safety Orders, Section 5143.
Every inside storage room shall be provided with either a gravity or a mechanical exhausting system. Such system shall commence not more than 12 inches above the floor and be designed to provide for a complete change of air within the room at least 6 times per hour. If a mechanical exhausting system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. An electric pilot light shall be installed adjacent to the switch if Category 1, 2 or 3 flammable liquids are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhausting outlet from the room, shall be on the exterior of the building in which the room is located.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. Amendment filed 10-9-86; effective thirtieth day thereafter (Register 86, No. 43).
2. Editorial correction of subsection (e) (Register 95, No. 21).