Cal. Code Regs. tit. 8, § 541
(a) General.
(1) Unless covered elsewhere in these Orders, every natural gas tank shall be provided with one or more spring-loaded safety relief valves set to open as follows with relation to the maximum allowable working pressure:
Type of Vessel
Minimum Safety Relief Valve Setting
Maximum Safety Relief Valve Setting
ASME Code Constructed Vessels with a factor of safety of 5 or more
100%
125%
ASME Code Constructed Vessels built with a factor of safety of less than 5
100%
110%
DOT Cylinders--Safety Relief Devices
As approved by Bureau of Explosives
All safety relief valves required by this Order shall be ASME labeled except for safety relief devices on DOT cylinders and safety relief valves as required in 537 (c)(3), which may be ASME or Underwriters' Laboratories rated and stamped.
(b) Compressed Natural Gas.
(c) Liquefied Natural Gas.