Cal. Code Regs. tit. 8, § 540
(c) The minimum relieving capacity of the safety relief valves shall be at least equal to the capacity marking on the vaporizer nameplate as required in Section 525 (c)(5). This marking shall be determined for exposure to external fire and shall be sufficient to prevent pressure in the vaporizer from exceeding 120 percent of the maximum working pressure. When determined by calculation, the applicable formula in Appendix A shall be used.
The safety relief valve discharge shall be led outside of the vaporizer building, if any, and be discharged at a safe place.
(e) Vaporizers shall not be installed inside of buildings unless the building is specifically designed for housing LNG vaporizers; in which case the building shall be constructed of non-combustible material and be adequately ventilated at both the floor line and ceiling. Ventilation shall be designed to prevent gasses lighter than air from being trapped at ceiling level.
Note: Ventilation is considered adequate when no mixture of flammable gases is permitted in concentrations exceeding 1/5 of the lower flammability limit for such mixture.