(a) General. Tanks and regulating equipment shall not be buried below ground unless written permission to do so has been obtained from the Division and the following special conditions are complied with:
(8) All buried tanks shall be completely uncovered for an inspection of all external surfaces at intervals of at least once every 3 years.
The intervals may be changed at the discretion of the Division if a test plate is buried adjacent to the tank and shows no appreciable corrosion on inspection after 3 years of service; provided, however, that every tank shall be uncovered at least every 15 years. The test plates shall be of the same material as the shell of the tank and shall be at least ¼ of the tank diameter in length and 6 inches wide and shall be buried in water-washed sand at least as deep as the lowest surface of the tank, and shall not be coated. Test plates shall be provided in accordance with the following table:
(b) Compressed Natural Gas.
(7) Wrap with Kraft paper.
Equivalent corrosion protection may be accepted at the discretion of the Division.
The exterior surfaces of CNG tanks shall be covered with an acceptable corrosion-resistant material.
Tanks will be considered acceptable when prepared and coated as follows:
(c) Liquefied Natural Gas.