Cal. Code Regs. tit. 8, § 531
(a) General.
(1) Except as provided elsewhere in these Orders, tanks, cylinders and regulating equipment used with natural gas storage and/or dispensing installations shall be located outside of buildings. Each individual tank or cylinder used for storage or dispensing natural gas shall be located with respect to the nearest important building, or line of adjoining property which may be built upon, or source of ignition, in accordance with the following table:
Capacity Per Storage Tank or Bank of Cylinders U. S. Gallons
Minimum Distance In Feet
Distance Between Above Ground Storage Tanks, Feet
To 500
10
3
501 To 2,000
25
3
2,001 To 30,000
50
5
30,001 To 70,000
75
¼ of Sum of Diameter of Adjacent Tanks with
70,001 To 90,000
100
a Minimum of 5 Feet
Note: At the discretion of the Division, tanks may be located a lesser distance from important buildings constructed of concrete or masonry materials.
(2) No stationary storage vessel shall be located less than 10 feet from the nearest street line or sidewalk, nor less than 50 feet from the nearest rail of any railroad main track.
The distance between underground tanks shall be not less than 12 inches.
(b) Compressed Natural Gas.
(c) Liquefied Natural Gas.