(a) LNG Vaporizers:
(1) Vaporizers having a volumetric capacity in excess of 1 U.S. gallon shall be either:
- (A) Constructed, inspected and stamped in accordance with the ASME Code unless the design and construction of the vaporizer are accepted by the Division as equivalent to the ASME Code, or;
- (B) Fabricated and tested in accordance with ANSI B-31.3 when artificial heat is not used for vaporization and when of welded construction consisting of continuous pipe or tubing and fittings not exceeding 6 inches inside diameter, or;
- (C) Made of threaded piping and pipe fittings and built to good engineering practice with a factor of safety of not less than 4, taking into account all imposed loadings.
- (2) Vaporizers and any part thereof, including carbureting devices, shall be designed for minimum as well as maximum temperatures and the maximum pressure that can be imposed with a safety factor of at least 4.
(3) Vaporizers having a volumetric capacity in excess of 1 U.S. gallon shall be stamped with the information required by the ASME Code and shall also include:
- (A) Head and shell thicknesses.
- (B) The words “For LNG.”
- (C) Heat exchange surface in square feet.
- (D) The vaporizer capacity per hour in U.S. gallons.
- (E) Minimum safety relief valve capacity in CFM air. (See Section 540 (c).)
- (b) Vaporizers made of pipe or tubing shall have a nominal diameter of 2 inches or less and shall have the information required in (C), (D) and (E) above stamped on a nameplate which shall be permanently attached to the vaporizer. This nameplate shall also show the manufacturer's name, year built and maximum allowable working pressure.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 13241, Health and Safety Code.
History
1. Amendment filed 12-8-72 as procedural and organizational; effective upon filing (Register 72, No. 50).
2. Amendment filed 11-7-75; effective thirtieth day thereafter (Register 75, No. 45).
3. Amendment filed 1-5-88; operative 2-4-88 (Register 88, No. 4).
4. Amendment of section heading, repealer of subsections (a)-(a)(5), subsection relettering, and amendment of Note filed 12-4-96; operative 1-3-97 (Register 96, No. 49).