Cal. Code Regs. tit. 3, § 6454
(a) When fumigating a structure, the fumigator shall ensure that the distance between the fumigated structure and its property line shall meet the following criteria and that no person, other than the fumigation crew, enters the area prescribed in either (1), (2), or (3) below during the treatment period:
(2) For fumigations utilizing more than 50 pounds, but less than 80 pounds, a distance in feet calculated using the following formula must exist:
5 times the total poundage of methyl bromide minus 240 feet; or
(d) Fumigators shall use the fumigant retention method specified in the table below for the application rate and poundage combinations utilized in the fumigation:
Methyl Bromide Application Rate Per 1,000 Cubic Feet of Structure
Total Pounds of M ethyl Bromide Applied in a 24-hour Period
Fumigant Retention Method
Up to 0.5 pounds
Not more than 20 pounds
“acceptable” tarpaulin
More than 20 pounds, but less than 1,000 pounds
“acceptable” tarpaulin, or if the structure is a concrete tilt-up, seal with vinyl coated self-adhesive tape
More than 0.5 pounds Up to 1.5 pounds
Not more than 50 pounds
“acceptable” tarpaulin and a side drape of either: (1) an “acceptable” tarpaulin or (2) an unused 4-mil disposable polyethylene sheet
More than 50 pounds, but less than 1,000 pounds
“acceptable” tarpaulin, or if the structure is a concrete tilt-up, seal with vinyl coated self-adhesive tape
More than 1.5 pounds Up to 3.0 pounds
Not more than 50 pounds
“acceptable” tarpaulin and a side drape of one unused 4-mil disposable polyethylene sheet
More than 50 pounds, but less than 1,000 pounds
“acceptable” tarpaulin, or if the structure is a concrete tilt-up, seal with vinyl coated self-adhesive tape
(i) Following treatment, the fumigated structure shall be aerated through convection tubing or ducting. Except as provided in subsection (j), the convection tubing or ducting outlet shall be located above the highest point of the roof as follows:
(j) If any nearby structure is taller than the fumigated structure and the distance between the structures is equal to or less than the distance indicated in the following table, the convection tubing or ducting outlet shall be located as high as the top of the roof of the tallest structure.
Total Pounds of Methyl Bromide Applied
Convective Tubing or Ducting Outlet Must Be As High As the Tallest Structure Within:
1-14
50 ft.
15-24
75 ft.
25-32
100 ft.
33-40
125 ft.
41-50
150 ft.
51-60
175 ft.
61-99
200 ft.
100-1,000
A distance in footage equal to 2 times the pounds of methyl bromide used
(k) When aerating a fumigated structure, a licensed Branch 1 operator or field representative shall ensure, from the initiation of the aeration procedure to completion of the steps described in (n) of this section, that persons not involved in the aeration process do not come within:
(2) For fumigations utilizing more than 50 pounds but less than 80 pounds, a distance in feet calculated using the following formula must exist:
5 times the total poundage of methyl bromide minus 240 feet; or
(l) Exhaust fans and convection tubing or ducting may be installed prior to aeration or when covering the structure with tarpaulins in preparation for fumigation. The exhaust fans, convection tubing, and installation of the fans and tubing shall meet the following requirements:
(n) The methyl bromide concentration shall be measured at the approximate center of the structure with a Fumiscope®, or similar instrument, that shall be located outside of the fumigated structure. (An instrument similar to a Fumiscope® may be used provided it can measure methyl bromide concentrations at the one ounce per 1,000 cubic feet [250 ppm] level.) Without entering the structure, the fumigator shall collect the methyl bromide sample for measurement through the use of tubing or ducting placed inside the structure and connected to the analytical instrument prior to the initiation of fumigation. The structure shall be aerated until the methyl bromide concentration has been reduced to 250 ppm or less (250 ppm is about one ounce per thousand cubic feet) while following the requirements listed below:
(2) If the fumigated structure's windows were closed during the fumigation:
This section supplements the methyl bromide fumigation requirements found in the Business and Professions Code and Title 16 of the California Code of Regulations, as well as directions for use given on methyl bromide product labeling.
Note: Authority cited: Sections 11456, 12976, 12981, 14005 and 14102, Food and Agricultural Code. Reference: Sections 11501, 12981, 14006 and 14102, Food and Agricultural Code.
1. Editorial renumbering of former section 2453(d) to section 6454 filed 8-13-85 (Register 85, No. 33).
2. Amendment of section heading and Note and new subsections (c)-(f) filed 4-14-92 as an emergency; operative 4-14-92 (Register 92, No. 18). A Certificate of Compliance must be transmitted to OAL 8-12-92 or emergency language will be repealed by operation of law on the following day.
3. Amendment of section heading and Note and new subsections (c)-(f) refiled 8-14-92 as an emergency; operative 8-14-92 (Register 92, No. 33). A Certificate of Compliance must be transmitted to OAL 12-12-92 or emergency language will be repealed by operation of law on the following day.
4. Amendment of section heading and Note and new subsections (c)-(f) refiled 12-18-92 as an emergency; operative 12-18-92 (Register 92, No. 51). A Certificate of Compliance must be transmitted to OAL 4-17-93 or emergency language will be repealed by operation of law on the following day.
5 Amendment of section heading and Note and new subsections (c)-(f) refiled 3-29-93 as an emergency; operative 3-29-93 (Register 93, No. 14). A Certificate of Compliance must be transmitted to OAL 7-27-93 or emergency language will be repealed by operation of law on the following day.
6. Repealer of subsections (c)-(f) and reinstatement of section heading and Note as they existed prior to emergency amendments filed 12-1-93, effective 7-28-93 by operation of Government Code section 11346.1(f) (Register 93, No. 49).
7. Editorial correction of History 3, 4, 5, and 6 (Register 94, No. 30).
8. Repealer and new section and amendment of Note filed 8-15-2000; operative 9-14-2000 (Register 2000, No. 33).